MicroReliant ICSArchitect SpecificationsSECTION 430 INTEGRATED INTERIOR COMMUNICATIONS AND ALARM SYSTEMS An ICS system shall specifically provide the equipment, control, and monitoring required for the Public Address (Announcing) system. In addition the system can be installed in conjunction with Interior Communication (Sound Powered Phone) provided special considerations for these systems be addressed by the design and installation of the integrated system. An ICS system, Multicom Reliant ICS or Equal, shall be furnished and installed by the communications contractor. A manufacturer-certified technician shall supervise the installation and testing of the equipment and shall be present during all official acceptance tests and trials, unless specifically approved otherwise. 2. INTEGRATED SYSTEM REQUIREMENTS There shall be a sufficient number of loudspeakers located throughout the vessel to meet minimum requirements for sound pressure levels as are specified by 46 CFR, ABS, or SOLAS. Loudspeakers located on weather decks shall be watertight and with terminations sealed for protection against the effects of wind and water. The system shall be provided with appropriate feeder distribution panels and branch circuit distribution panels. Each system shall have at least one feeder for each vertical fire zone with at least one branch circuit for each deck level and shall be, where possible, separated into port and starboard branch circuits so as to provide uninterrupted operation in the event of damage to a portion of the vessel/system. Power requirements for the integrated system shall at a minimum meet the requirements for the power source and emergency power source for general emergency alarms as is called out in Subpart 113.25-6 in 46 CFR. |
|
| Copyright © Multicom 1975 - 2008, All Rights Reserved | |