FMM-101

Monitor Module with FlashScan

• Built-in type identification automatically identifies the device as a monitor module to the AFC-600.
• Powered directly by two-wire FACP. No additional power required.
• High noise (EMF/RFI) immunity.
• Tinned, stripped leads for ease of wiring.
• Direct-dial entry of address.

The FMM-101 Monitor Module (made by Notifier for integration with Multicom ICS systems) can be installed in a single-gang junction directly behind the monitored unit. Its small size and light weight allow it to be installed without rigid mounting. The FMM-101 is intended for use in intelligent, two-wire systems where the individual address of each module is selected using rotary switches. It provides a two-wire initiating device circuit for normally-open-contact fire alarm and security devices. The FMM-101 can be used to replace MMX-101 module in existing systems.

Applications

Use to monitor a single device or a zone of four-wire smoke detectors, manual fire alarm pull stations, waterflow devices, or other normally-open dry-contact devices. May also be used to monitor normally-open supervisory devices with special supervisory indication at the control panel. Monitored circuit/device is wired as an NFPA Style B (Class B) Initiating Device Circuit. A 47 K ohm End-of-Line Resistor (provided) terminates the circuit.

Operation

Each FMM-101 uses one of 159 available module addresses on an SLC loop. It responds to regular polls from the control panel and reports its type and the status (open/normal/short) of its Initializing Device Circuit (IDC).

Specifications

• Nominal operating voltage: 15 to 32 VDC.
• Average operating current: 375µA (LED flashing).
• EOL resistance: 47K ohms.
• Temperature range: 32ºF to 120ºF (0ºC to 49ºC).
• Humidity range: 10% to 93% non condensing.
• Dimensions: 1.3" (33.02 mm) high x 2.75" (69.85 mm) wide x 0.5" (12.70 mm) deep.
•Wire length: 6" (152.4 mm) minimum.