Products < Fire Alarms & Sensors < FMM-1

FMM-1

Monitor Module with FlashScan
FMM-1 Monitor Module with FlashScan

• Built-in type identification automatically identifies the device as a monitor module to the control panel.
• Powered directly by two-wire SLC loop. No additional power required.
• High noise (EMF/RFI) immunity.
• SEMS screws with clamping plates for ease of wiring.
• Direct-dial entry of address 01-159 (01-99 on traditional systems).
• LED flashes green during normal operation (this is a programmable option) and latches on steady red to indicate alarm.

The FMM-1 Monitor Module (made by Notifier for integration with Multicom ICS systems) is intended for use in intelligent, two-wire systems, where the individual address of each module is selected using the built-in rotary switches. It provides either a two-wire or four-wire fault-tolerant Initiating Device Circuit (ICD) for normally-open-contact-fire alarm and supervisory devices.The module has a panel-controlled LED indicator. The FMM-1 can be used to replace MMX-1 modules in existing systems.

Applications

Use to monitor a zone of four-wire smoke detectors, manual fire alarm pull stations, waterflow devices or other normally-open dry-contact alarm activation devices. May also be used to monitor normally open supervisory devices with special supervisory indication at the control panel. Monitored circuit may be wired as an NFPA Style B (Class B) or Style D (Class A) Initiating Device Circuit. A 47K ohm End-of-Line Resistor (provided) terminates the Style B circuit. No resistor is required for supervision of the Style D circuit. Maximum IDC loop length is 2,500 ft./762 m (20 ohms maximum).

Operation

Each FMM-1 uses one of 159 available module addresses on an SLC loop. It responds to regular polls from the control panel and reports its type and the status (open/normal/short) of its Initiating Device Circuit (IDC). A flashing LED indicates that the module is in communication with the control panel. The LED latches steady on alarm (subject to current limitations on the loop).

Specifications

• Nominal operating voltage: 15 to 32 VDC.
• Maximum current draw: 5.1 mA (LED on).
• Average operating current: 400 µA (LED flashing).
• EOL resistance: 47 ohms.
• Temperature range: 32ºF to 120ºF (0ºC to49ºC).
• Humidity range: 10% to 93% non condensing.
• Dimensions: 4.5" (114.3 mm) high x 4" (101.6 mm) wide x 1.25" (31.75 mm) deep. Mounts to a 4" (101.6 mm) square x 2.125" (53.975 mm) deep box.